GV2ME Motor Circuit Breaker Data Reference Table
Dec 31,2021 | simplybuy industrial
Motor circuit breakers from 0.06 to 15 kW / 400 V, with screw clamp terminals | |||||||||||
Deca - Frame 2 (ref. GV2ME) with pushbutton control | |||||||||||
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 |
Setting range of thermal trips (2) |
Magnetic tripping current Id ± 20 % |
Reference | ||||||||
400/415 V | 500 V | 690 V | |||||||||
P | Icu | Ics (1) | P | Icu | Ics (1) | P | Icu | Ics (1) | |||
kW | kA | % | kW | kA | % | kW | kA | % | A | A | |
– | – | – | – | – | – | – | – | – | 0.1…0.16 | 1.5 | GV2ME01 |
0.06 | ★ | ★ | – | – | – | – | – | – | 0.16…0.25 | 2.4 | GV2ME02 |
0.09 | ★ | ★ | – | – | – | – | – | – | 0.25…0.40 | 5 | GV2ME03 |
0.12 | ★ | ★ | – | – | – | 0.37 | ★ | ★ | 0.40…0.63 | 8 | GV2ME04 |
0.18 | ★ | ★ | – | – | – | – | – | – | |||
0.25 | ★ | ★ | – | – | – | 0.55 | ★ | ★ | 0.63…1 | 13 | GV2ME05 |
0.37 | ★ | ★ | 0.37 | ★ | ★ | – | – | – | 1…1.6 | 22.5 | GV2ME06 |
0.55 | ★ | ★ | 0.55 | ★ | ★ | 0.75 | ★ | ★ | |||
– | – | – | 0.75 | ★ | ★ | 1.1 | ★ | ★ | |||
0.75 | ★ | ★ | 1.1 | ★ | ★ | 1.5 | 3 | 75 | 1.6…2.5 | 33.5 | GV2ME07 |
1.1 | ★ | ★ | 1.5 | ★ | ★ | 2.2 | 3 | 75 | 2.5…4 | 51 | GV2ME08 |
1.5 | ★ | ★ | 2.2 | ★ | ★ | 3 | 3 | 75 | |||
2.2 | ★ | ★ | 3 | 50 | 100 | 4 | 3 | 75 | 4…6.3 | 78 | GV2ME10 |
3 | ★ | ★ | 4 | 10 | 100 | 5.5 | 3 | 75 | 6…10 | 138 | GV2ME14 |
4 | ★ | ★ | 5.5 | 10 | 100 | 7.5 | 3 | 75 | |||
5.5 | 15 | 50 | 7.5 | 6 | 75 | 9 | 3 | 75 | 9…14 | 170 | GV2ME16 |
– | – | – | – | – | – | 11 | 3 | 75 | |||
7.5 | 15 | 50 | 9 | 6 | 75 | 15 | 3 | 75 | 13…18 | 223 | GV2ME20 |
9 | 15 | 40 | 11 | 4 | 75 | 18.5 | 3 | 75 | 17…23 | 327 | GV2ME21 |
11 | 15 | 40 | 15 | 4 | 75 | – | – | – | 20…25 | 327 | GV2ME22 (3) |
15 | 10 | 50 | 18.5 | 4 | 75 | 22 | 3 | 75 | 24…32 | 416 | GV2ME32 |
(1) As % of Icu.
(2) The thermal trip setting must be within the range marked on the graduated knob.
(3) Maximum rating which can be mounted in enclosures GV2MC or MP.
★ > 100 kA.
Motor circuit breakers from 3/4 to 20 HP / 460 V, with screw clamp terminals | ||||||||||
Deca - Frame 2 (ref. GV2ME) with pushbutton control | ||||||||||
Thermal setting (A) |
Maximum Horsepower ratings | Group Motor applications |
Reference | |||||||
Single-Phase | Three-Phase | |||||||||
115 V | 200 V | 230 V | 115 V | 200 V | 230 V | 460 V | 575 V | Max. Fuse or Circuit breaker (A) |
||
0.1…0.16 | – | – | – | – | – | – | – | – | 450 | GV2ME01 |
0.16…0.25 | – | – | – | – | – | – | – | – | 450 | GV2ME02 |
0.25…0.40 | – | – | – | – | – | – | – | – | 450 | GV2ME03 |
0.40…0.63 | – | – | – | – | – | – | – | – | 450 | GV2ME04 |
0.63…1 | – | – | – | – | – | – | – | 1/2 | 450 | GV2ME05 |
1…1.6 | – | – | 1/10 | – | – | – | 3/4 | 3/4 | 450 | GV2ME06 |
1.6…2.5 | – | 1/6 | 1/6 | – | 1/2 | 1/2 | 1 | 1.5 | 450 | GV2ME07 |
2.5…4 | 1/8 | 1/4 | 1/3 | – | 3/4 | 3/4 | 2 | 3 | 450 | GV2ME08 |
4…6.3 | 1/4 | 1/2 | 1/2 | 3/4 | 1 | 1.5 | 3 | 5 | 450 | GV2ME10 |
6…10 | 1/2 | 1 | 1.5 | 1 | 2 | 3 | 5 | 7.5 | 450 | GV2ME14 |
9…14 | 3/4 | 2 | 2 | 2 | 3 | 3 | 10 | 10 | 450 | GV2ME16 |
13…18 | 1 | 2 | 3 | 2 | 5 | 5 | 10 | 15 | 450 | GV2ME20 |
17…23 | 1.5 | 3 | 3 | 3 | 5 | 7.5 | 15 | 20 | 450 | GV2ME21 |
20…25 | 2 | – | – | – | 7.5 | 7.5 | 15 | 20 | 450 | GV2ME22 |
24…32 | 2 | 5 | 5 | 5 | 7.5 | 10 | 20 | 25 | 450 | GV2ME32 |