Schneider GV2P Motor Circuit Breaker Data Reference Table
Dec 31,2021 | simplybuy industrial
Motor circuit breakers from 0.06 to 15 kW / 400 V, with screw clamp terminals | |||||||||||
Deca - Frame 2 (ref. GV2P): control by rotary knob | |||||||||||
Screw clamp terminals | |||||||||||
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 |
Setting range of thermal trips (2) |
Magnetic tripping current Id ± 20 % |
Reference | ||||||||
400/415 V | 500 V | 690 V | |||||||||
P | Icu | Ics (1) | P | Icu | Ics (1) | P | Icu | Ics (1) | |||
kW | kA | % | kW | kA | % | kW | kA | % | A | A | |
– | – | – | – | – | – | – | – | – | 0.1…0.16 | 1.5 | GV2P01 |
0.06 | ★ | ★ | – | – | – | – | – | – | 0.16…0.25 | 2.4 | GV2P02 |
0.09 | ★ | ★ | – | – | – | – | – | – | 0.25…0.40 | 5 | GV2P03 |
0.12 | ★ | ★ | – | – | – | 0.37 | ★ | ★ | 0.40…0.63 | 8 | GV2P04 |
0.18 | ★ | ★ | – | – | – | – | – | – | |||
0.25 | ★ | ★ | – | – | – | 0.55 | ★ | ★ | 0.63…1 | 13 | GV2P05 |
0.37 | ★ | ★ | 0.37 | ★ | ★ | – | – | – | 1…1.6 | 22.5 | GV2P06 |
0.55 | ★ | ★ | 0.55 | ★ | ★ | 0.75 | ★ | ★ | |||
0.75 | ★ | ★ | 1.1 | ★ | ★ | 1.5 | 8 | 100 | 1.6…2.5 | 33.5 | GV2P07 |
1.1 | ★ | ★ | 1.5 | ★ | ★ | 2.2 | 8 | 100 | 2.5…4 | 51 | GV2P08 |
2.2 | ★ | ★ | 3 | ★ | ★ | 4 | 6 | 100 | 4…6.3 | 78 | GV2P10 |
3 | ★ | ★ | 5 | 50 | 100 | 5.5 | 6 | 100 | 6…10 | 138 | GV2P14 |
5.5 | ★ | ★ | 7.5 | 42 | 75 | 9 | 6 | 100 | 9…14 | 170 | GV2P16 |
– | – | – | – | – | – | 11 | 6 | 100 | |||
7.5 | 50 | 50 | 9 | 10 | 75 | 15 | 4 | 100 | 13…18 | 223 | GV2P20 |
9 | 50 | 50 | 11 | 10 | 75 | 18.5 | 4 | 100 | 17…23 | 327 | GV2P21 |
11 | 50 | 50 | 15 | 10 | 75 | – | – | – | 20…25 | 327 | GV2P22 |
15 | 50 | 50 | 18.5 | 10 | 75 | 22 | 4 | 100 | 24…32 | 416 | GV2P32 |
(1) As % of Icu.
(2) The thermal trip setting must be within the range marked on the graduated knob.
★ > 100 kA.
How to use the table : select your load operating voltage, then select its standard power value (below, in the same
column). The appropriate circuit breaker is in the extreme right column, in the corresponding row.
Exemple: GV2P04 can protect 0.12 and 0.18 kW under 400/415 V, and 0.18 kW under 440 V, and 0,37 kW under
690 V. No 500 V standard power value can fit GV2P04.
Motor circuit breakers up to 50 HP / 600 V, UL 60947-4-1 type E | ||||||||||
Deca - Frame 2 (ref. GV2P) with rotary handle | ||||||||||
Thermal setting (A) |
Maximum Horsepower ratings | Group Motor applications |
Reference | |||||||
Single-Phase | Three-Phase | |||||||||
115 V | 200 V | 230 V | 115 V | 200 V | 230 V | 460 V | 575 V | Max. Fuse or Circuit breaker (A) |
||
0.1…0.16 | – | – | – | – | – | – | – | – | 450 | GV2P01 |
0.16…0.25 | – | – | – | – | – | – | – | – | 450 | GV2P02 |
0.25…0.40 | – | – | – | – | – | – | – | – | 450 | GV2P03 |
0.40…0.63 | – | – | – | – | – | – | – | – | 450 | GV2P04 |
0.63…1 | – | – | – | – | – | – | – | 1/2 | 450 | GV2P05 |
1…1.6 | – | – | 1/10 | – | – | – | 3/4 | 3/4 | 450 | GV2P06 |
1.6…2.5 | – | 1/6 | 1/6 | – | 1/2 | 1/2 | 1 | 1.5 | 450 | GV2P07 |
2.5…4 | 1/8 | 1/4 | 1/3 | – | 3/4 | 3/4 | 2 | 3 | 450 | GV2P08 |
4…6.3 | 1/4 | 1/2 | 1/2 | 3/4 | 1 | 1.5 | 3 | 5 | 450 | GV2P10 |
6…10 | 1/2 | 1 | 1.5 | 1 | 2 | 3 | 5 | 7.5 | 450 | GV2P14 |
9…14 | 3/4 | 2 | 2 | 2 | 3 | 3 | 10 | 10 | 450 | GV2P16 |
13…18 | 1 | 2 | 3 | 2 | 5 | 5 | 10 | 15 | 450 | GV2P20 |
17…23 | 1.5 | 3 | 3 | 3 | 5 | 7.5 | 15 | 20 | 450 | GV2P21 |
20…25 | 2 | – | – | – | 7.5 | 7.5 | 15 | 20 | 450 | GV2P22 |
24…32 | 2 | 5 | 5 | 5 | 7.5 | 10 | 20 | 25 | 450 | GV2P32 |