Range | PowerPact |
---|---|
Product name | PowerPact H |
Product or Component Type | Circuit breaker |
Device Application | Distribution |
Line Rated Current | 40 A |
Number of Poles | 3P |
Protected poles description | 3t |
Control Type | Toggle |
Breaking capacity code | J |
Breaking capacity | 100 kA 240 V AC 50/60 Hz UL 489 65 kA 480 V AC 50/60 Hz UL 489 25 kA 600 V AC 50/60 Hz UL 489 20 kA 250 V DC UL 489 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-3 |
Network Frequency | 50/60 Hz |
[Ics] rated service breaking capacity | 100 kA 220/240 V AC 50/60 Hz IEC 60947-2 65 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 25 kA 500/525 V AC 50/60 Hz IEC 60947-2 20 kA 250 V DC IEC 60947-2 20 kA 500 V DC IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
Trip unit technology | Thermal-magnetic |
Magnetic tripping current | 850 A |
Magnetic hold current | 400 A |
Continuous current rating | 80 % |
[Ui] rated insulation voltage | 750 V IEC 60947-2 |
Suitability for isolation | Yes IEC 60947-2 |
Utilisation category | Category A |
AWG gauge | AWG 14...AWG 3/0 aluminium/copper terminal |
Local signalling | Switched off (OFF) 1 trip indicator green) |
Mounting mode | I-Line bracket) |
Mounting Support | Bracket |
Electrical connection | I-Line connection line Lugs load |
Terminal identifier | AL150HD |