Range | PowerPact |
---|---|
Product name | PowerPact H |
Product or Component Type | Circuit breaker |
Device Application | Distribution |
Line Rated Current | 25 A |
Number of Poles | 3P |
Protected poles description | 3t |
Control Type | Toggle |
Breaking capacity code | D |
breaking capacity | 25 kA 240 V AC 50/60 Hz UL 489 18 kA 480 V AC 50/60 Hz 14 kA 600 V AC 50/60 Hz 20 kA 250 V DC |
[Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-3 |
Network Frequency | 50/60 Hz |
[Ics] rated service breaking capacity | 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 20 kA 250 V DC IEC 60947-2 20 kA 500 V DC IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
trip unit technology | Thermal-magnetic |
Magnetic tripping current | 750 A |
Magnetic hold current | 350 A |
Continuous current rating | 80 % |
[Ui] rated insulation voltage | 750 V IEC 60947-2 |
suitability for isolation | Yes IEC 60947-2 |
Utilisation category | Category A |
AWG gauge | AWG 14...AWG 3/0 aluminium/copper terminal |
local signalling | Switched off (OFF) 1 trip indicator green) |
mounting mode | I-Line bracket) |
Mounting Support | Bracket |
electrical connection | I-Line connection line Lugs load |
Terminal identifier | AL150HD |
Mounting Height | 4.5 in (114.30 mm) |
tightening torque | 44.25 lbf.in (5 N.m) 0.00…0.01 in² (2.5…6 mm²) (AWG 14...AWG 10) 123.91 lbf.in (14 N.m) 0.02…0.15 in² (10…95 mm²) (AWG 8...AWG 3/0) |
number of slots | 2 auxiliary switch OF plug-in) 1 alarm switch SD plug-in) 1 overcurrent trip switch SDE plug-in) 1 voltage release MN or MX plug-in) |
Power wire stripping length | 0.63 in (16 mm) |
Color | Black |
Height | 6.42 in (163 mm) |
Width | 4.09 in (104 mm) |
Depth | 3.39 in (86 mm) |
Net Weight | 4.85 lb(US) (2.2 kg) |
Quantity per Set | 1 |
Phase connection | ABC |
Communication interface | Modbus Ethernet |
Circuit breaker application | HACR rated |