| Range | TeSys |
|---|---|
| Product Name | TeSys VARIO |
| Device Short Name | V |
| Product Type | Switch body |
| Mounting Support | Plate Symmetrical rail |
| Performance Level | High performance |
| Number of Poles | 3P |
| Contact Type and Composition | 3 NO |
| Network type | AC DC |
| Network frequency | 50/60 Hz |
| [Ue] IEC Rated Operational Voltage | 690 V AC 50/60 Hz |
| IEC Rated Operational Power in W | 3 kW at 400...415 V (AC-3) 4 kW at 500 V (AC-3) 1.5 kW at 230...240 V (AC-3) 5.5 kW at 500 V (AC-23A) 5.5 kW at 690 V (AC-3) 7.5 kW at 690 V (AC-23A) 3 kW at 230...240 V (AC-23A) 4 kW at 400...415 V (AC-23A) |
| [Ie] Rated Operational Current | 8.1 A AC-23 Ue: 400 V |
| [Ith] Conventional Free Air Thermal Current | 12 A |
| [Ithe] Conventional Enclosed Thermal Current | 10 A |
| Making capacity ( I Rms) | 120 A at 400 V AC-21A 120 A at 400 V AC-22A 120 A at 400 V AC-23A |
| Breaking Capacity | 120 A at 400 V (AC-21A) 120 A at 400 V (AC-22A) 120 A at 400 V (AC-23A) |
| Rated Conditional Short Circuit Current | 10 kA at 400 V - associated fuse 12 A aM 10 kA at 400 V - associated fuse 12 A gG |
| [Icm] Rated Short Circuit Making Capacity | 1 kA at 400 V at Ipeak |
| Intermittent duty | 30 |
| Suitability for isolation | Yes |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Icw] rated short-time withstand Rms current | 300 A at 400 V duration: 1 s |
| Mechanical Durability | 100000 cycles |
| Electrical Durability | 100000 cycles AC-21 30000 cycles DC-1 30000 cycles DC-2 30000 cycles DC-3 30000 cycles DC-4 30000 cycles DC-5 |
| IEC Terminal Connection | Power circuit: screw clamp terminals10 mm² - solid Power circuit: screw clamp terminals6 mm² - flexible - with cable end |
| Tightening Torque | Power circuit: 2.1 N.m - on screw clamp terminals |
| Height | 74 mm |
| Width | 55 mm |
| Depth | 60 mm |
| Product Weight | 0.2 kg |