| Product Series | Acti 9 |
|---|---|
| product name | IC65 |
| product type | Miniature Circuit Breaker |
| Product short name | IC65H |
| Number of poles | 4P |
| Applications | Distribution protection |
| Number of protective poles | 4 |
| Rated current[In] | 10 A at 30 °C |
| Grid type | AC |
| Trip unit type | Thermomagnetic |
| tripping curve | C |
| Breaking capacity | 10 kA Icn at 400 V AC 50/60 Hz per pole in accordance with GB/T 10963.1 10 kA Icn at 400 V AC 50/60 Hz in each pole in accordance with IEC 60898-1 |
| Usage categories | AC type |
| Isolation function | Be applicable |
| Grid frequency | 50/60 Hz |
| Rated operating voltage [Ue] | 400 V AC 50/60 Hz |
| Magnetic trip limits | 5...10xIn |
| Current limiting level | 3 |
| Rated insulation voltage [Ui] | 500V AC |
| Rated impulse withstand voltage [Uimp] | 6 kV |
| Contact position indication | Have |
| Control type | Handle |
| local signaling | On/off indication |
| Installation type | Locking clip lock |
| Installation method | DIN rail mounting |
| Width (multiples of 9mm) | 8 |
| high | 94mm |
| depth | 78.5mm |
| net weight | 500g |
| Mechanical life | 20000 times |
| Electrical life | 10000 times |
| Wiring capability | Tunnel terminals for top or bottom connections 1…25 mm² Solid solid wire without wire terminals Tunnel terminals for top or bottom wires 1…16 mm² Flexible wire (optional) with or without wire terminals |
| Stripping length | 14 mm power loop: |
| Tightening torque | 2.5 Nm power circuit: |
| Leakage current protection | (Required) additional assembly |