| Range | EasyLogic |
|---|---|
| Product name | EasyLogic PM2200 |
| Product or Component Type | Power meter |
| Device short name | PM2230 |
| Device Application | Power monitoring Sub billing |
| Power quality analysis | total harmonic distortion up to the 31st harmonic |
| Accuracy | 1 reactive energy IEC 62053-24 0.5S active energy IEC 62053-22 5 harmonic distortion (I THD & U THD) |
| Measurement current | 5…6000 mA |
| Measurement voltage | 35…480 V AC 50/60 Hz between phases 20…277 V AC 50/60 Hz between phase and neutral 480…999000 V AC 50/60 Hz with external VT |
| Frequency measurement range | 45…65 Hz |
| [Us] rated supply voltage | 80...277 V AC 45...65 Hz +/- 10 % 100...277 V DC +/- 10 % |
| Network Frequency | 60 Hz 50 Hz |
| Ride-through time | 50 ms 120 V AC typical 50 ms 230 V AC typical 50 ms 125 V DC typical |
| Line Rated Current | 5 A 1 A |
| Maximum power consumption in VA | 8 VA 277 V AC |
| Maximum power consumption in W | 3.3 W power lines (AC)) 3.3 W 277 V power lines (DC)) |
| input impedance | Current (impedance <= 0.3 mOhm) Voltage (impedance > 5 MOhm) |
| Tamperproof of settings | Protected by access code |
| Display Type | Backlit LCD |
| Display colour | Monochrome |
| Display Resolution | 128 x 128 pixels |