Product Series | TeSys Deca |
---|---|
Product type | contactor |
Contactor application areas | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads and resistance furnaces |
Usage categories | AC-1 AC-3 |
Number of poles | 3P |
Rated operating voltage [Ue] | Power loop: <= 1000 V AC 25...400 Hz Power loop: <= 460 V DC |
Rated operating current [Ie] | 275 A 40 °C) at <= 440 V AC AC-1 for mains circuit 205 A 40 °C) at <= 440 V AC AC-3 for mains circuit |
[Uc] control circuit voltage | 110 V AC 50/60 Hz |
Motor power (kW) | 100 kW at 1000 V AC 50/60 Hz (AC-3) 63 kW at 220/240 V AC 50/60 Hz (AC-3) 110 kW at 380/400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660/690 V AC 50/60 Hz (AC-3) |
Model | LC1D |
Loop contact type | 3 NO |
Installation method | Base plate installation Rail installation |
High | 174 mm |
Width | 168.5 mm |
Depth | 181 mm |
Net weight | 5.2 kg |