range | TeSys |
---|---|
range of product | TeSys D |
product or component type | Contactor |
device short name | LC1D |
contactor application | Motor control Resistive load |
poles description | 3P |
[Ue] rated operational voltage | Power circuit: 1000 V AC 25...400 Hz |
[Ie] rated operational current | 95 A (at <60 °C) at <= 440 V AC-3 for power circuit 125 A (at <60 °C) at <= 690 V AC-1 for power circuit 95 A (at <60 °C) at <= 440 V AC-3e for power circuit |
pole contact composition | 3 NO |
contact compatibility | M11 |
protective cover | With |
auxiliary contact composition | 1 NO + 1 NC |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
overvoltage category | III |
control circuit type | AC at 50/60 Hz |
coil technology | Without built-in suppressor module |
average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
minimum switching current | 5 mA for signalling circuit |
minimum switching voltage | 17 V for signalling circuit |
maximum operating rate | 3600 cyc/h 60 °C |
insulation resistance | > 10 MOhm for signalling circuit |
mechanical durability | 4 Mcycles |
operating altitude | 0...3000 m |