Product Series | Acti 9 |
---|---|
product name | IC65 |
product type | Miniature Circuit Breaker |
product short name | IC65N |
number of poles | 3P |
Applications | Distribution protection |
Number of guard poles | 3 |
Rated current [In] | 25 A at 30 °C |
Grid type | AC |
Trip unit type | Thermomagnetic |
Trip curve | C |
Breaking capacity | 6 kA Icn at 400 V AC 50/60 Hz per pole conforming to GB/T 10963.1 6 kA Icn at 400 V AC 50/60 Hz per pole conforming to IEC 60898-1 |
use category | AC |
isolation function | Be applicable |
grid frequency | 50/60Hz |
Rated working voltage [Ue] | 400 V AC 50/60 Hz |
Magnetic trip limit | 5...10 x In |
current limiting level | 3 |
Rated insulation voltage [Ui] | 500V AC |
Rated impulse withstand voltage [Uimp] | 6kV |
Contact position indication | Have |
control type | Handle |
local signal indication | On/off indicator |
installation type | Locking clip lock |
installation method | DIN rail mounting |
Width (multiples of 9mm) | 6 |
high | 94mm |
depth | 78.5mm |
net weight | 325g |
Mechanical life | 20000 times |
Electrical life | 10000 times |
Wiring capacity | Tunnel terminal top or bottom 1…25 mm² Solid wire without wire terminal Tunnel terminal top or bottom 1…16 mm² flexible wire (optional) with or without wire terminal |
Stripping length | 14 mm power return: |
Tightening torque | 2.5 Nm power circuit: |
Leakage current protection | (Required) additional assembly |
Standards compliant | IEC 60898-1 GB 10963.1 |
certified product | CE CCC CCS |
IP protection | IP20 complies with screwed |
pollution level | 3 |
Overvoltage category | IV |
Moisture resistance | 2 Conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
operating temperature | -35…70°C |